E41-306 · Other Selection · Steam Pipe Flange Gasket · ★★★
The flange joint of a steam pipe (1.6MPa, 260℃) leaked after 2 months of operation; on teardown inspection the asbestos-rubber gasket was found carbonized and brittle, causing seal failure.
An asbestos-rubber sheet gasket was selected (thickness 3mm, applicable temperature ≤200℃). The steam temperature of 260℃ exceeds the gasket's upper temperature limit by 60℃. At 260℃, the organic binder (rubber) in the asbestos-rubber sheet decomposes and carbonizes, and the gasket loses its elasticity. Under the flange bolt preload (20kN), the now-inelastic gasket cannot compensate for the slight separation of the flange faces (thermal expansion and pressure separate the flanges by about 0.05mm), creating a leakage path. The leaking steam (260℃) directly scours the gasket edge, accelerating its destruction. After 2 months the gasket was completely carbonized, its compression ratio dropped from 20% to 5%, and the seal failed.
① Steam-pipe gasket selection: temperature ≤200℃→asbestos-rubber sheet, 200~400℃→spiral-wound metal gasket\n② For 260℃ in this case, a spiral-wound metal gasket should be used (304 stainless steel + graphite tape)\n③ The spiral-wound metal gasket is applicable from -200~800℃ and withstands pressure ≥6.4MPa\n④ Flange face roughness Ra3.2~6.3μm (spiral-wound gaskets are not demanding on flange faces)\n⑤ Tighten bolts to the standard torque (M20 bolt torque 250Nm, tightened in a diagonal criss-cross sequence)
FT_Machine Design Handbook