E41-759 · Other Selection Topics · Boiler Drum Differential Pressure Level Gauge · ★★★
The differential pressure level gauge on a boiler drum indicated a level 200mm below the actual level. The operator added too much water and the drum was overfilled.
The balance vessel (condensing pot) of the differential pressure level gauge was installed 200mm below the drum center line (the design requires it to be level with the drum center line). With the balance vessel below the drum center line the height difference of the condensing water column in the positive pressure impulse line produces an additional differential pressure ΔP=ρ×g×Δh=1000×9.8×0.2=1.96kPa, which corresponds to a level error of 200mm of water column. The gauge therefore always reads 200mm below the true level, the operator feeds water according to the displayed value, the actual level rises and the drum is eventually overfilled. Steam with water carryover enters the superheater and the superheater is damaged.
1) Re-check all the parameters against the correct selection specification;
2) Confirm that the duty load, environment and life all meet the design requirements;
3) Select a reliable brand and a suitable model;
4) Verify the installation and operating conditions;
5) Inspect and maintain the equipment at regular intervals after commissioning.