E41-781 · Other Selection · Ground Failure · ★★★★
The motor ground wire (copper, 4 mm² cross-section, 3 m long) failed to conduct leakage current effectively when the motor leaked; the RCCB did not trip.
The ground-wire cross-section is 4 mm² (GB 50169 requires ≥50% of the motor power-wire size; motor power wire 10 mm² → needs ≥5 mm²), 4 < 5, so the section is insufficient. Ground resistance R = ρ×L/A = 1.72×10⁻⁸×3/(4×10⁻⁶) = 0.013 Ω (very low), the ground-wire resistance is negligible. During leakage the ground-loop impedance is mainly the ground electrode resistance (GB requires ≤4 Ω); at 220 V, 4 Ω gives leakage current I = 220/4 = 55 A, far above the RCCB trip value (30 mA), so the RCCB should trip correctly. The actual reason it did not: the ground-wire-to-electrode connection bolt corroded (galvanized bolt severely corroded in damp environment over 2 years), contact resistance rose from 0.01 Ω to 100 Ω; total loop resistance = 0.013 + 100 + 4 ≈ 104 Ω, leakage current I = 220/104 = 2.1 A < 10 A (breaker trip current), so the breaker did not trip. A 2.1 A leakage current is enough to cause electric shock danger (100 mA through a person is fatal); grounding failed.
① Recheck all parameters per correct selection specifications
② Confirm that operating loads, environment, and service life all meet design requirements
③ Select reliable brands and appropriate models
④ Verify installation and operating conditions
⑤ Perform periodic inspection and maintenance after commissioning