E41-782 · Other Selection · Ground Mixing · ★★★★
During a thunderstorm, multiple I/O modules of the PLC control system burned out; common-mode voltage reached 1000 V.
The PLC control system ground (working ground) shares a ground electrode with the lightning-protection ground (shared resistance ≤1 Ω, meeting the requirement). But the down-conductor from the lightning rod (air terminal) is only 0.5 m from the PLC ground wire (requires ≥3 m); during a lightning strike (current 100 kA, rise time 0.25 μs) the magnetic field around the down-conductor is H = I/(2π×r) = 100000/(2×3.14×0.5) = 31.8 kA/m. The changing field induces a very high transient voltage in the PLC ground wire U = M×dI/dt = 0.5×10⁻⁶×100000/(0.25×10⁻⁶) = 200 V (M, mutual inductance, about 0.5 μH); plus the potential rise on the ground wire (lightning current × ground resistance = 100 kA×1 Ω = 100 kV), so the transient potential on the ground wire reaches above 100 kV. Although the ground wires are equipotentially bonded (all equipment on one ground grid), the high-frequency component in the ground wire couples through stray capacitance to the PLC signal lines → the I/O module isolation barrier breaks down → module burns out.
① Recheck all parameters per correct selection specifications
② Confirm that operating loads, environment, and service life all meet design requirements
③ Select reliable brands and appropriate models
④ Verify installation and operating conditions
⑤ Perform periodic inspection and maintenance after commissioning