E41-784 · Other Selection · Expansion Bolt Loosening · ★★★★
A suspended air-conditioning unit was fixed to a concrete floor slab with M12 expansion bolts (Q235); after 2 months of operation, 2 bolts loosened and fell out.
An M12 expansion bolt in C30 concrete has a recommended pull-out capacity about 8 kN each (standard embedment depth 70 mm). The AC unit weighs 1.2 t; 4 bolts give total 32 kN, safety factor S = 32/12 = 2.67 (unit gravity 1.2×9.8 = 11.8 kN, plus 20% running vibration → 14.2 kN), 2.67 > 2 (standard safety factor), theoretically safe. But the holes were drilled at the slab edge (100 mm from the slab end, requirement ≥200 mm); the concrete-edge cone-failure tensile capacity is only 50% of the interior (about 4 kN each). Also the bolt embedment was only 40 mm (standard 70 mm), hole too shallow (drill did not fully penetrate), capacity dropping another 50% → 2 kN each. 4 bolts total 8 kN < 14.2 kN → loosen and fall one by one under vibration.
① Recheck all parameters per correct selection specifications
② Confirm that operating loads, environment, and service life all meet design requirements
③ Select reliable brands and appropriate models
④ Verify installation and operating conditions
⑤ Perform periodic inspection and maintenance after commissioning
FT_Machine Design Handbook