E41-795 · Other Selection · Sensor Detection Failure · ★★★
The photoelectric sensor frequently missed workpieces on the conveyor line (about 1 missed per 100 pieces), and its status indicator light flickered.
The photoelectric sensor (diffuse-reflective type, detection distance 500 mm) was mounted on the side of the conveyor line, with the beam at a 30° angle to the conveyor surface. When a workpiece (black plastic, reflectivity about 5%) passed by, the reflected light intensity received by the sensor was about 500 Lux (ambient light 1000 Lux), giving a signal-to-noise ratio = 500/1000 = 0.5 (< 1); ambient light interference caused the sensor to misjudge. The sensor mounting angle should be adjusted to 45°–60° (to concentrate the reflected light), or a light shield should be added in front of the sensor (to reduce ambient-light interference), or it should be replaced with a through-beam photoelectric sensor (unaffected by workpiece color and reflectivity).
① Recheck all parameters per correct selection specifications
② Confirm that operating loads, environment, and service life all meet design requirements
③ Select reliable brands and appropriate models
④ Verify installation and operating conditions
⑤ Perform periodic inspection and maintenance after commissioning