Knowledge Base › Selection Error Cases › Solenoid valve failing to actuate due to incorrect coil voltage selection (solenoid valve voltage)

Solenoid valve failing to actuate due to incorrect coil voltage selection (solenoid valve voltage)

E41-796 · Other Selection · Solenoid Valve Voltage Error · ★★★

Problem Description

The replacement solenoid valve (coil 220 V AC) was connected to a PLC output (24 V DC), so the valve did not actuate.

Root Cause

A 220 V AC solenoid valve has a coil resistance of about 500 Ω. At 24 V DC the current is I = 24/500 = 0.048 A = 48 mA, and the coil power is P = 24×0.048 = 1.15 W, far below the rated power (at 220 V AC, P = 220²/500 = 96.8 W). The electromagnetic force produced by the 48 mA current, F ∝ I²×N (N = number of coil turns), is only about (48 mA/440 mA)² = 0.012 = 1.2% of the rated electromagnetic force. This 1.2% force is insufficient to overcome the valve spool spring force (about 3 N), so the solenoid valve does not actuate.

Corrective Solution

① Recheck all parameters per correct selection specifications
② Confirm that operating loads, environment, and service life all meet design requirements
③ Select reliable brands and appropriate models
④ Verify installation and operating conditions
⑤ Perform periodic inspection and maintenance after commissioning

Checklist

Reference

FT_Machine Design Handbook