E41-807 · Other Selection · Fan Reversal · ★★★
After installing the motor's independent cooling fan, the motor temperature rose from a normal 75 °C to 105 °C; inspection found the fan was running in reverse.
The independent cooling fan's three-phase power wiring had the wrong phase sequence (two phases swapped), so the fan rotated opposite to the design direction. When an axial fan runs in reverse, its airflow is only 30–40% of forward rotation (the blade mounting angle is designed for forward blowing; in reverse the blades have negative angle of attack → stall → airflow drops sharply). The motor cooling airflow dropped from 1.5 m³/s to 0.5 m³/s, cooling efficiency fell by 67%, and the motor temperature rise went from 50 K to 80 K.
① Recheck all parameters per correct selection specifications
② Confirm that operating loads, environment, and service life all meet design requirements
③ Select reliable brands and appropriate models
④ Verify installation and operating conditions
⑤ Perform periodic inspection and maintenance after commissioning
FT_Machine Design Handbook