E41-819 · Other Selection · Improper Grounding Ring Installation · ★★★★
A grounding ring (conductive fiber brush, Φ60 mm) was installed at the VFD motor shaft end, but bearing electrical erosion still appeared after 3 months of operation.
The grounding ring was installed at the motor shaft extension end (coupling side), with the ring-to-shaft contact point at the end of the shaft extension. The shaft current generated by the VFD (about 5 A) flows along the shaft to the grounding ring → ground wire → earth. But the bearing (non-drive end) lies between the grounding ring and the VFD, so part of the shaft current (about 1 A) flows through the non-drive-end bearing → motor housing → ground wire → earth. A grounding ring at the shaft extension end cannot bypass all shaft current; some current still passes through the bearing. Correct installation: the grounding ring should be mounted at the bearing near the VFD side (to bypass shaft current between the bearing and the VFD), or insulated bearings should be used (both drive and non-drive ends insulated).