Low temperature reading caused by insufficient temperature probe insertion depth (temperature probe)

E41-822 · Other Selection · Insufficient Probe Insertion · ★★★

Problem Description

The pipe temperature sensor (PT100, armored, diameter Φ6 mm) had an insertion depth of 30 mm (pipe inner diameter 200 mm), and its reading was 8 °C lower than the actual temperature.

Root Cause

The temperature sensor insertion depth should be at least 1/3 of the pipe inner diameter (200/3 = 67 mm); actual was 30 mm < 67 mm. The sensor probe was located within the boundary layer near the pipe wall (boundary layer thickness about 20 mm), where the temperature gradient is large (center fluid temperature 80 °C, wall temperature 65 °C, difference 15 °C). With the probe at 30 mm inside the boundary layer, the actual measured temperature was about 72 °C (8 °C lower than the center fluid temperature).

Corrective Solution

① Recheck all parameters per correct selection specifications
② Confirm that operating loads, environment, and service life all meet design requirements
③ Select reliable brands and appropriate models
④ Verify installation and operating conditions
⑤ Perform periodic inspection and maintenance after commissioning

Checklist

Reference