Bolt Too Short Gives Insufficient Engagement and Causes the Flange to Pull Out and Leak

E42-120 · Threaded Connection Loosening · Piping Flange Bolt M16 · ★★

Problem Symptom

The bolt bottoms out after only 3 threads of engagement and pulls out and leaks after vibration

Root Cause

[Insufficient Engagement] The bolt is too short and the engagement length is <0.8d, so few threads engage and each thread carries a high load.
[Pull Out] The alternating tensile force shears off the few engaged threads and the joint separates.
[Design Omission] The engagement length was not calculated and the bolt was wrongly selected.

Correct Solution

1) Re-select a longer bolt with an engagement length ≥0.8d;
2) Match the flange thickness and bolt length;
3) Measure the engagement allowance before assembly;
4) Apply the torque for the flange class;
5) Check the flange sealing face with dye penetrant;
6) Pressure test and hold to check for leaks;
7) Add anti-loosening measures for vibration duty;
8) Include the engagement length in the assembly card.

Checklist

References

GB/T 9124 Steel Pipe Flanges — Technical Conditions