E42-437 · Corrosion Failure · N-3000 condenser copper tube · ★★★
N-3000 condenser (HSn70-1) copper tube: dezincification after 3 years, wall perforated and leaked; repaired twice a year
[Dezincification] Cooled water contaminated, selective dezincification of brass 0.1mm/a. [Perforation] Wall 1mm thick, leak in 3 years. [Design Omission] No arsenic inhibitor, non-resistant material; safety factor 1.2 (should be ≥2.0).
1) Change copper tube to arsenic brass/titanium;
2) Add corrosion and scale inhibitor;
3)CoolingWater treatment;
4) Eddy-current test quarterly;
5) Measure wall thickness;
6) Rubber-ball cleaning;
7) Limit flow velocity;
8) Replace tubes at end of life.
GB/T 8890-2015