E44-006 · Excessive Piping Resistance & Pressure Drop · Steam control valve · ★★
For the DN25 valve the actual Kv was too small: 0.8MPa upstream and 0.2MPa downstream, so the 0.6MPa throttling drop caused the downstream temperature control to fail with a ±15℃ temperature swing
[Kv Matching] The actual flow requires KV=12 but the valve has KV=6; the opening would still have to be above 90% and the throttling drop accounts for 80% of the system.
[Characteristic Distortion] A high pressure drop ratio flashes the downstream flow and cavitates, so the flow characteristic is distorted and out of control.
[Design Omission] The valve was not selected with Cv=Q√(ρ/Δp) and the turndown ratio was not checked for R≥30, so the valve size was too small.
1) Recalculate the required Kv=12 with Cv=Q√(ρ/Δp) and fit a larger valve (Kv≥12), because the original Kv=6 is only half the requirement and an opening above 90% still falls short; this places the valve in the 30% to 70% working range where it is adjustable;
2) Check the turndown ratio R≥30, because a small R means the full range is reached at a small opening and the linearity is poor, thereby guaranteeing regulating resolution over the whole range;
3) Allocate the system pressure drop so that the valve accounts for 30% to 50%, because an 80% share makes the high pressure drop ratio cause flashing and cavitation and distort the characteristic, thereby spreading the drop across the piping so the downstream condition stays stable;
4) Provide at least 10D/5D of straight pipe upstream and downstream to develop the flow, because an undeveloped upstream turbulence makes the measured Kv drift, thereby making the valve characteristic repeatable;
5) Select an equal-percentage flow characteristic to match the temperature control loop, because the equal-percentage characteristic has low gain at small openings and suits the large inertia of a temperature loop, thereby reducing closed-loop swing;
6) Install a differential pressure transmitter across the valve to monitor the operating region of Δp, because a Δp out of range heralds cavitation or a blockage, thereby giving early warning;
7) Commission the temperature control to verify an outlet swing ≤±2℃ (against ±15), because once the valve linearity is restored the loop can be tuned, thereby keeping the temperature under control;
8) Write the Kv and R into the control valve data sheet, because selection parameters scattered across documents are easily mismatched, thereby keeping the procurement and installation consistent.
GB/T 17213.1-2015 Industrial Process Control Valves