E44-313 · Excessive Pipe Resistance and Pressure Drop · Two parallel legs, one long and one short · ★★
A 0.05MPa resistance difference between the two branches lets the short leg take 70% of the flow and the long leg only 30%, starving the long branch's process feed.
[Bias Flow] Branch resistance differences split flow inversely with resistance, and the short leg steals the flow.
[Shortfall] The long leg gets only 30%, under-feeding the process.
[Design Omission] No symmetric layout and no balancing valves — biased flow in the parallel legs.
1) Make the two branches symmetric in length and bore, since one long/one short at a 0.05 resistance split gave 70/30 and starved the long leg — thus balancing flow by symmetry;
2) Add a balancing valve on the long leg to trim resistance, since the resistance split caused bias — thus balancing it;
3) Check each branch hf to equalize resistance, since unequal resistance biases flow — thus equalizing it;
4) Add flow meters to watch each branch, since bias flow is hard to detect — thus monitoring flow;
5) Add an orifice plate to the short leg to limit flow, since the short leg steals flow — thus throttling it;
6) Equalize pressure at the pump discharge header, since the pressure difference drives the bias — thus balancing it;
7) Recalibrate balancing valves on schedule, since drift causes bias — thus rebalancing;
8) Write symmetry and balancing into the design, since the original asymmetry was the root cause of bias — thus locking it in at design.
GB/T 20801.3-2020 Design code for industrial metallic piping