E44-150 · Other · Non-Conductive-Gasket Flange Piping · ★★★
The insulating gasket broke the bonding jumper; static charge built up and discharged as a spark, creating an ignition risk.
[Bond Break] The insulating gasket breaks electrical continuity.
[Spark] Static voltage exceeding the limit discharges.
[Design Omission] No bonding jumper and no grounding; a spark hazard remained.
1) Fit a bonding jumper across the flange to keep continuity; the insulating gasket breaks the jumper, static voltage overshoots and sparks, so the jumper conducts it away;
2) Add a jumper across the non-conductive gasket and ground it; the gasket does not conduct, so add bonding;
3) Keep system grounding resistance ≤10Ω and measure it periodically; high resistance does not discharge, so test periodically;
4) Design against static for flammable areas; sparks ignite, so make it explosion-proof;
5) Discharge body static before operating; people carry static, so discharge first;
6) Limit flow velocity to cut static generation; high velocity builds charge, so limit speed;
7) Verify jumper continuity and absence of spark on commissioning; design requirements need measured confirmation, so confirm at delivery;
8) Bring bonding and grounding into anti-static design; the original omission was the root cause of sparks, so the design must include it.
GB 12158-2006 General guide for preventing static electricity accidents