E44-151 · Other · Atmospheric-Tank Nitrogen Blanketing · ★★★
The blanketing valve failed and opened the tank to atmosphere; oxygen rose to 8%, over the safety limit.
[Blanket Lost] The valve jammed and breathing drew in oxygen.
[Over Limit] Oxygen accumulation above 5% is hazardous.
[Design Omission] No oxygen monitoring and no blanketing redundancy; oxygen ran over limit.
1) Provide redundant blanketing valves to hold a slight positive pressure; a jammed valve lets breathing draw in oxygen and accumulation over 5% is hazardous, so use redundant blanketing;
2) Fit oxygen-content monitoring and alarm on the tank; over 8% is hazardous, so monitor and alarm;
3) Fit check valves on the nitrogen line to prevent suck-back; a gas interruption sucks in oxygen, so add check valves;
4) Interlock the breather valve with the blanket for coordinated tuning; mis-coordination draws in oxygen, so interlock them;
5) Stabilize the nitrogen supply pressure; low pressure cannot hold the blanket, so regulate pressure;
6) Periodically exercise the blanketing valve; a jam fails, so check it periodically;
7) Verify oxygen content within the safety limit on commissioning; design requirements need measured confirmation, so confirm at delivery;
8) Bring blanketing and oxygen monitoring into tank design; the original failure was the root cause of excess oxygen, so the design must include it.
GB 50160-2008 Fire-prevention design standard for petrochemical enterprises