E44-152 · Other · Tank-Bottom Drain Valve · ★★
The drain valve was not fully closed; a micro-leak pooled and contaminated the floor, with odor.
[Not Tight] Foreign matter on the plug prevents tight shutoff.
[Seepage] A micro-leak pools and soils.
[Design Omission] No double valve and no leak detection; seepage contaminated.
1) Provide two drain valves in series to prevent improper closure; foreign matter on the plug leaks slowly and soils, so double valves back it up;
2) Add a leak-collection sump after the valve; a micro-leak becomes visible, so collect and detect it;
3) Tag out the closed valve to prevent accidental opening; an accidental opening leaks, so tag it;
4) Periodically inspect the floor for seepage and odor; leakage soils gradually, so check periodically;
5) Choose a drain-valve type with reliable sealing; a poor type leaks easily, so select the valve;
6) Route drainage to a treatment system rather than direct discharge; direct discharge pollutes, so route to treatment;
7) Verify tight shutoff on commissioning; design requirements need measured confirmation, so confirm at delivery;
8) Bring double valves and leak detection into drain design; the original improper closure was the root cause of seepage, so the design must include it.
GB/T 20801-2020 Pressure piping code