E44-1072 · Other · Steam Trap · ★★
Valve leaking, steam lost, low efficiency.
[Mechanism] The trap leaks internally; live steam bypasses with the condensate, losing heat energy and dropping system pressure.
[Calculation] A DN25 trap leaks 15kg/h of steam internally; annual steam loss is 130t, and leakage rises at 0.2MPa back pressure.
[Design Omission] No correct selection, no seal check, and no leak detection.
1) Replace with a free-float type (tight shutoff replacing the old one); leakage loses steam, and the new type seals, restoring tightness;
2) Check tight shutoff (zero leak is acceptance); leakage loses steam, and a tight check protects the seal;
3) Add a side drain (online on blockage); a blockage loses function, and the side drain protects discharge;
4) Raise back-pressure stability (≥0.1MPa to prevent leakage); low pressure leaks, and raising pressure protects, suppressing leakage;
5) Run a seal test (leak ≤1kg/h); leakage was untested, and measured data confirms tightness;
6) Install steam-flow monitoring (alarm on leak); leakage first shows as steam loss, and early warning catches it;
7) Control installation orientation in operation (forbid reverse mounting); reverse mounting leaks, and correct orientation prevents it;
8) Record selection and tightness check in the maintenance card; the root cause of trap leakage was wrong selection and no tightness check, so maintenance must gate it.
GB/T 12250-2005 Steam traps