E44-1071 · Other · Sampling Line · ★★
Line blocked, sample lost, analysis biased.
[Mechanism] The sampling line is thin and never blown; impurities deposit and plug it, the sample lags and distorts, and analysis is biased.
[Calculation] The DN8 sampling line, 15m long, was 40% blocked; lag was 8min (should be ≤2); sample concentration deviated 15%, causing misjudgment.
[Design Omission] No purging, no lag check, and no line shortening.
1) Set timed purging (0.4MPa compressed-air back-blow); a blockage causes lag, and blowing clears it, restoring the sample;
2) Check lag ≤2min (was 8); a long line causes lag, and timing check guarantees it, making the sample accurate;
3) Add a drain valve (purge dead sample before sampling); accumulation causes lag, and draining gives fresh sample;
4) Shorten the line distance (≤5m); long distance causes lag, and shortening speeds it, cutting lag;
5) Run a sample-comparison test (difference vs direct take ≤5%); bias was unchecked, and measured confirmation proves accuracy;
6) Install sample-flow monitoring (alarm on lag); a blockage first shows as lag, and early warning catches it;
7) Control the purge interval in operation (every shift); long intervals cause blockage, so controlled purging prevents it;
8) Record purge and timing in the sampling specification; the root cause of sample distortion was no purging and a long line, so the specification must gate it.
GB/T 25915.1-2010 Cleanrooms