E44-1074 · Other · Impulse Line · ★★
Line pooled, liquid, pointer biased.
[Mechanism] The impulse line was not sloped toward the transmitter; high points pooled liquid and the pressure indication ran low.
[Calculation] The 12m impulse line, reverse-sloped, pooled 30%; the indication ran 8% low, causing a control mis-action.
[Design Omission] No sloped drainage, no drain valve, and no slope check.
1) Provide sloped drainage (1:20 toward the transmitter); pooling biases the reading, and sloped drainage restores accuracy;
2) Check the slope (forbid reverse slope); a flat slope pools, and a checked slope drains, leaving no pooling;
3) Add a drain valve (at the lowest point); pooling lags, and draining gives an accurate reading;
4) Shorten the line distance (≤6m); long distance pools, and shortening speeds it, cutting lag;
5) Run a calibration test (difference vs standard ≤1%); bias was unchecked, and measured confirmation proves accuracy;
6) Install indication monitoring (alarm on bias); pooling first shows as bias, and early warning catches it;
7) Keep take-off points low in operation (forbid high-point pooling); high points pool, and low take-off drains it, preventing bias in service;
8) Record slope drainage and drain valve in the impulse-line specification; the root cause of pooling was no slope and no drain, so the specification must gate it.
GB/T 2624.1-2006 Flow measurement