E44-1075 · Other · Cooling Tower · ★★
Drift, water lost, water reduced.
[Mechanism] The tower had no drift eliminator or high air velocity; droplets were carried out by the airflow, losing circulating water.
[Calculation] Airflow 20000m³/h with no drift eliminator; drift rate 0.02%, water loss 10t/h, and make-up water demand high.
[Design Omission] No drift elimination, no air-velocity check, and no fill packing.
1) Add a drift eliminator (baffle type, 150mm); drift loses water, and elimination recovers it;
2) Check air velocity ≤3m/s (was 4.5); high velocity causes drift, and a checked velocity relieves it, suppressing drift;
3) Fit even fill packing (uniform water distribution); uneven distribution drifts, and even packing stabilizes it;
4) Control water level steadily (forbid overflow); a high level drifts, and level control stabilizes it, suppressing drift;
5) Run a water-recovery test (drift rate ≤0.005%); loss was unchecked, and measured recovery confirms it;
6) Install level/flow monitoring (alarm on loss); drift first shows as loss, and early warning catches it;
7) Control water distribution in operation (even distribution); bias causes drift, and even distribution prevents it;
8) Record drift elimination and even packing on the cooling-tower drawing; the root cause of drift loss was no eliminator and high air velocity, so the drawing must gate it.
GB/T 7190.1-2008 Glass-fiber-reinforced plastic cooling towers