E44-1076 · Other · Expansion Tank · ★★
Tank overflowing, leaking, level high.
[Mechanism] The expansion tank was undersized or the level control failed; water expanded on heating and overflowed, losing water.
[Calculation] System water 5m³; thermal expansion 2% requires 0.1m³ capacity, but the tank held only 0.05m³, overflowing 0.05m³ per event.
[Design Omission] No volume check, no level control, and no overflow recovery.
1) Check sufficient volume (≥ expansion 0.1m³); small volume overflows, and adequate volume stops it;
2) Control water level (float to limit height); a high level overflows, and level control stabilizes it, suppressing overflow;
3) Add overflow recovery (route back to the make-up tank); overflow loses water, and recovery returns it;
4) Stabilize make-up (forbid running dry); shortage causes suction loss, and stable make-up keeps water;
5) Run a volume test (full without overflow); overflow was unchecked, and measured capacity confirms it;
6) Install level monitoring (alarm on high level); overflow first shows as a high level, and early warning catches it;
7) Keep the expansion pipe clear in operation (forbid blockage); a blockage overflows, and a clear pipe prevents it;
8) Record volume and level control on the water-system drawing; the root cause of expansion-tank overflow was small volume and no level control, so the drawing must gate it.
GB/T 50050-2017 Industrial circulating cooling water