E44-1081 · Other · Flame Arrester · ★★
Blocked, poor venting, deficient.
[Mechanism] Dirt accumulated on the arrester element surface, shrinking the flow area, raising pressure drop, and leaving venting insufficient.
[Calculation] The element face was 50% blocked; the flow area halved; ΔP rose 0.08MPa, and flow fell 30%.
[Design Omission] No matched flow/resistance selection, no cleaning, and no inspection.
1) Choose a matched flow/resistance type (large-area arrester element); blockage weakens venting, and a matched selection restores flow;
2) Check pressure drop ≤0.02MPa (was 0.08); high drop means blockage, and a checked drop protects venting;
3) Add a clean-out port (removable for cleaning); accumulation blocks, and cleaning clears it;
4) Enlarge the element face (larger area); a small face blocks, and a larger face prevents it;
5) Run a flow-through test (measured ΔP≤0.02); poor venting was unchecked, and measured flow confirms it;
6) Install differential-pressure monitoring (alarm on blockage); a blockage first shows as pressure rise, and early warning catches it;
7) Control medium cleanliness in operation (pre-filter); dirt blocks, and cleanliness slows it, preventing blockage;
8) Record matched selection and clean-out on the arrester drawing; the root cause of blockage was poor selection and no cleaning, so the drawing must gate it.
GB/T 13347-2010 Flame arresters for petroleum gas pipelines