E44-1083 · Other · Water Seal · ★★
Seal lost, crossover, gas mixed.
[Mechanism] The water-seal level was low or evaporated dry; the seal failed and gas crossed over.
[Calculation] Seal depth 50mm (should be ≥100); level dropped 30mm; seal pressure only 0.3kPa< pipe pressure 0.5, and gas crossed over.
[Design Omission] No makeup water, no level control, and no inspection.
1) Provide automatic makeup (float constant level); low level loses the seal, and makeup restores it;
2) Control level ≥100mm (was 50); a low level loses the seal, and level control holds it, sealing tightly;
3) Add overflow (prevent overfull overflow); overflow loses the seal, and overflow equalizes, stabilizing the level;
4) Check seal depth ≥2× pipe pressure (was insufficient); shallow seal loses it, and checked depth holds it, sealing tightly;
5) Run a seal test (hold 0.5kPa without crossover); failure was untested, and measured sealing confirms it;
6) Install level monitoring (alarm on low level); failure first shows as a low level, and early warning catches it;
7) Prevent evaporation loss in operation (insulate against evaporation); evaporation loses the seal, and anti-evaporation holds it;
8) Record makeup and level control on the water-seal drawing; the root cause of seal failure was no makeup and low level, so the drawing must gate it.
GB/T 50074-2014 Petroleum depot design code