E44-1118 · Miscellaneous · Thermometer · ★★
Too-short insertion, measurement, offset
[Mechanism] The thermometer is inserted too shallow, reading only the pipe-wall temperature rather than the medium, so the indication runs low.
[Calculation] Required insertion depth is ≥150mm but actual is only 60mm; the reading runs 15℃ below the true value, a 20% error.
[Design Omission] No insertion-depth check, no center-position control, no zero check, and no accuracy test.
1) Set insertion depth ≥150mm (was 60), since too-short insertion causes error and a deeper insert reads true, restoring accuracy;
2) Position it at the center (pipe centerline), since off-center reading biases it and center position reads true, giving accurate indication;
3) Add a thermowell (protects against erosion), since erosion biases the reading and a sheath stabilizes it, stabilizing measurement;
4) Calibrate the zero (ice-point calibration), since offset causes error and a true zero reads true, giving accurate indication;
5) Run an accuracy test (error ≤1%), since without proof accuracy is unknown and a measured test confirms it, setting measurement on data;
6) Fit reading monitoring (alarm on offset), since too-short insertion first shows as a low reading for early warning, monitoring deviation;
7) Set a calibration interval (yearly), since long service drifts and scheduled calibration prevents it, guarding against offset in service;
8) Write insertion depth and position into the thermometer card, since too-short insertion stems from inadequate depth plus off-center position, closing the loop on the card.
GB/T 4213-2008 Temperature instruments