E44-1117 · Miscellaneous · Vortex Flowmeter · ★★
Vibration, reading, offset
[Mechanism] The vortex meter is weakly supported near a vibrating pump; pipe vibration overlaps the vortex-shedding frequency, biasing the count.
[Calculation] Pump vibration is 15Hz and the vortex frequency is f=St·v/d; vibration adds to the signal amplitude, giving a count error of 6% (should be ≤1).
[Design Omission] No support added, no frequency avoidance, no straight-run check, and no accuracy test.
1) Add supports to isolate vibration (rigid mounts), since vibration causes error and support stabilizes it, restoring accuracy;
2) Keep flow velocity steady (cut pulsation), since high speed causes vibration and steady flow quiets it, suppressing vibration;
3) Check the straight runs (10D upstream, 5D downstream), since bends bias the reading and straight runs read true, giving accurate indication;
4) Avoid resonance (move the support to change f_n), since resonance amplifies vibration and frequency avoidance keeps it safe, preventing error;
5) Run an accuracy test (error ≤1%), since without proof accuracy is unknown and a measured test confirms it, setting indication on data;
6) Fit vibration monitoring (alarm on threshold), since vibration first shows as amplitude for early warning, monitoring and alerting;
7) Add damping (absorb vibration), since vibration causes error and damping reduces it, stabilizing the signal;
8) Write support and frequency avoidance into the flowmeter drawing, since the bias stems from no support plus near resonance, closing the loop at the drawing.
GB/T 2624.1-2006 Flow measurement