E44-345 · Excessive Piping Resistance and Pressure Drop · Direct supply over a 40m vertical rise · ★★
A 40m elevation difference gives 0.4MPa static head at the low end, wastes energy in throttling valves, and needs 40m of added pump head at the high end
[Mechanism] A 40m vertical rise makes low-end static pressure high and demands added head at the top.
[Calculation] To control the high low-end pressure, valves throttle and waste energy.
[Design Omission] No vertical zoning and no pressure reduction - the elevation head was wasted.
1) Zone the supply vertically every 10m, since direct 40m supply gave 0.4 low-end static head and heavy throttling loss, zoning to cut static head;
2) Fit a pressure-reducing valve in the low zone to stabilize pressure, since high static head wastes energy, reducing pressure;
3) Dedicate a pump to the high zone to add head, since 40m must be made up, a high-zone pump;
4) Check each zone's hf independently, since zoning shortens the runs, computing per zone;
5) Fit pressure monitoring per zone, since zones differ in pressure, monitoring each zone;
6) Avoid throttling one point for the whole system, since throttling wastes energy, adjusting by zone;
7) Match pump head per zone, since zones need different heads, matching by zone;
8) Write vertical zoning into the design, since the missing zoning was the root cause, closing the loop at design.
GB/T 20801.3-2020 Design code for industrial metallic piping