E44-1023 · Excessive Piping Resistance & Pressure Drop · Piping · ★★
Small diameter, high resistance, large pressure drop
[Mechanism] An undersized pipe diameter raises the velocity, increases the friction factor and the friction loss, so the system pressure drop exceeds the design and the terminal flow is short.
[Calculation] Design Q=200m3/h with DN150 selected giving v=3.1m/s (design value 2.0), lambda=0.025, L=200m; hf=lambda*L/d*v^2/2g=0.025x200/0.15x3.1^2/19.6=1.62m, 0.8m above design, with a 40% terminal pressure drop.
[Design Omission] The design velocity was not calculated, the friction loss was never verified, and no margin was allowed.
1) Enlarge the pipe to DN200 (v falls from 3.1 to 1.8m/s, hf from 1.62 to 0.55m); the original DN150 at v=3.1m/s exceeded the design velocity and drove hf 0.8m above design, so enlarging the pipe reduces the resistance and the terminal pressure drop returns to the design value;
2) Verify the design velocity at 1.5~2.5m/s (take 2.0m/s and back-calculate d); a high velocity raises hf and the check quantifies the sizing;
3) Recalculate hf=lambda*L/d*v^2/2g using lambda from the friction chart; the original calculation omitted lambda so hf came out low, and calculating it makes the check accurate;
4) Raise the pump head with a 20% margin (the original margin was insufficient); a high resistance leaves the terminal under-pressurised and raising the head compensates, securing the flow;
5) Carry out a resistance test (measure the actual DeltaP against the calculation); without the test the actual resistance is unknown, so measurement validates it and the data fixes the resistance;
6) Control the flow at or below the design value of 200m3/h (above that the velocity and resistance rise); excess raises hf and controlling it slows the rise, keeping the resistance steady in operation;
7) Provide a drainage slope (1:100 towards the low point); deposits raise roughness and resistance, and the slope keeps the line clean, preventing roughness from rising;
8) Write the diameter calculation and velocity verification into the calculation sheet; the root cause of the small diameter was a missing design-velocity calculation with no hf verification, so the calculation sheet closes the loop.
GB/T 20801.3-2020 Design Code for Industrial Metallic Piping