E44-109 · Valve Selection and Internal Leakage · Globe valve J41H · ★★
Long-term throttling at 20% opening scours the plug 0.8mm deep; internal leakage 0.5L/min and control lost
[Mechanism] A high-velocity flow at small opening erodes the sealing face.
[Calculation] Throat v=Q/A; at small opening v rises 5× and erosion ∝v².
[Design Omission] No dedicated throttling valve provided - internal leakage followed.
1) Provide a dedicated throttling valve for control, since a globe valve at small opening erodes, giving a dedicated valve for the duty;
2) Hardface the plug (e.g. Stellite), since a hard face resists erosion, cutting grooving;
3) Limit operation to opening ≥30%, since at small opening v rises 5× and erosion ∝v², easing scouring;
4) Add a downstream enlargement to lower velocity, since lower v weakens erosion, protecting the seal;
5) Fit online leak detection, since internal leakage is detectable, treating it early;
6) Periodically lap the sealing faces, since scouring leaves them uneven, restoring seating pressure;
7) Test leakage ≤0.1L/min at commissioning, since the design requires measured proof, confirming before handover;
8) Put throttling-vs-isolation duties into the valve spec, since misuse was the main cause, locking it in to prevent recurrence.
GB/T 12235-2007 Steel globe valves and lift check valves for petrochemical industry