E44-161 · Valve Selection and Internal Leakage · Globe Valve · ★★
Installed backwards, the medium hits the plug from behind; shutoff is poor with internal leakage and the stem rises
[Mechanism] Flow opposite to design direction prevents tight shutoff.
[Calculation] The plug is blown open by the reverse flow.
[Design Omission] It was not installed per flow direction and had no flow marking - leakage followed.
1) Install the globe valve per the flow marking (low inlet, high outlet), since backwards installation prevented shutoff and leaked, installing with flow;
2) Check the flow arrow before installation, since it was fitted backwards, verifying direction;
3) Mark a permanent flow arrow on the body, since without a mark it goes backwards, marking direction;
4) Verify zero internal leakage at shutoff during commissioning, since the design requires measured proof, confirming before handover;
5) Use a bidirectional valve for reversing duty, since flow direction varies, bidirectional;
6) Train installers to read flow direction, since human error caused the reverse fit, training them;
7) Keep a shutoff test record, since leakage is hard to spot, recording the test;
8) Put flow-direction checking into the installation procedure, since the unchecked fit was the root cause, the procedure must include it.
GB/T 12235-2019 Oil and gas industry - Flanged steel globe valves