E44-253 · Valve Selection and Internal Leakage · Concentric butterfly valve D71X-10 DN300 · ★★
Internal leakage 12L/min after shutoff; disc/seat overlap -1.5mm (design ≥2mm); pressure drops 0.2MPa in 15min
[Mechanism] A 2mm stem-center offset eccentricizes the disc, causing one-sided interference with the seat; it can't close fully, leaving a 0.8mm gap.
[Calculation] Insufficient overlap drops the seating pressure p < the required p_q, so the line seal doesn't conform.
[Design Omission] Disc eccentricity and overlap were not checked and seat resilience was not controlled - the butterfly valve leaked.
1) Correct stem-center offset to ≤0.5mm, since the 2mm offset caused one-sided interference and a 0.8mm gap, centering the disc to shut tight;
2) Ensure disc/seat overlap ≥2mm, since -1.5mm overlap dropped seating pressure p < the required p_q and the line seal didn't conform, bringing it into contact to close the gap;
3) Switch to an interference-compressed resilient rubber seat, since elasticity compensates slight eccentricity and fills the gap, sealing even with minor offset;
4) Raise closing torque to 1.5× rated, since the low torque left the disc short of full seat, pressing it fully home;
5) Add guides in the body bore to stop disc wobble, since wobble worsens one-sided interference, aligning the motion;
6) Run bidirectional seat tests (zero leakage), since interference leakage is one-sided and a single-direction test misses it, checking both ways;
7) Periodically inspect disc deformation and seat aging, since aging lowers resilience and erodes overlap, replacing in time;
8) Put eccentricity and overlap into assembly inspection, since the lack of control was the root cause, shipping only conforming valves.
GB/T 12238-2008 Flanged and wafer-resilient-seated butterfly valves