E44-258 · Valve Selection and Internal Leakage · Thermostatic-dynamic trap CS19H-16C DN25 · ★★
The trap vents steam continuously, failing to block steam while draining condensate; condensate back-up cuts heat-exchanger efficiency 20% and live steam blows off at about 40kg/h
[Mechanism] On a low-pressure high-load duty a thermostatic-dynamic trap (suited to small load, high pressure) was misused; the disc chatters and won't seat.
[Calculation] Erosion of disc and seat worsens the seal, and steam blows out with the condensate.
[Design Omission] Selection ignored load/differential pressure and no test tube was fitted - the trap blew steam.
1) Switch to a float or bimetallic trap (suited to high load at low pressure), since the thermostatic-dynamic type is only best at small load/high pressure and the mismatch caused chatter, selecting by duty;
2) Size the orifice for 2× the load, since undersizing backed up condensate and cut heat transfer 20%, holding margin for free drainage;
3) Fit a strainer upstream to protect the disc from erosion, since particles damaged the seal and blew off 40kg/h, protecting the seat;
4) Add a trap test tube to watch leakage, since live venting is hard to spot, making it visible;
5) Add a parallel bypass with an isolating valve, so the line needn't be shut off for maintenance, enabling isolated replacement;
6) Periodically measure the steam fraction of the discharge, since leaking steam is direct loss, quantifying it;
7) Use a thermostatic trap on low-pressure systems to save steam, since its operating temperature is controllable with little steam loss, saving energy;
8) Put the sizing formula into the design, since ignoring load and differential pressure was the root cause, closing the loop at design.
GB/T 22654-2008 Steam traps - Technical specifications