E44-280 · Valve Selection and Internal Leakage · Inverted-bucket steam trap FT43-16 DN25 · ★★
The bucket jammed at the top and would not drop, venting steam continuously without draining; pooled condensate cut heat-exchanger efficiency by 15%.
[Jam] The bucket-to-body guide rusted and seized, so the bucket would not follow the water level and the valve stayed closed.
[Steam Blow] The valve stuck open so steam vented straight through.
[Design Omission] No guide to prevent jamming and no cleaning interval set — the inverted-bucket trap jammed.
1) Protect the guide rod from rust seizing and clean it periodically; rust jammed the bucket at the top, venting steam straight and cutting efficiency 15%, so make it follow the water level;
2) Fit a strainer upstream against jamming; particles damage the guide, so protect it;
3) Periodically drain pooled condensate; pooling worsens heat transfer, so drain freely;
4) Switch to a float trap that needs no guide; the float has no bucket-jam risk, so drain reliably;
5) Add a sight glass on the discharge to watch venting; straight steam blow is hard to notice, so make it visible;
6) Measure the live-steam fraction in the discharge; leaked steam is lost energy, so quantify it;
7) Add low-temperature heat tracing against rust binding; cold promotes sticking, so insulate;
8) Include cleaning in maintenance; the unset interval was the cause of jamming, so gate it in O&M.
GB/T 22654-2008 Steam traps - Technical specifications