E44-296 · Valve Selection and Internal Leakage · Float steam trap FT14-16 DN20 · ★★
A capacity of only 0.2t/h (actual 0.6t/h) let condensate back up and cut heat-exchange efficiency by 18%.
[Undersized] The trap capacity < the condensate generation rate, so water backs up.
[Drop] Pooled water covers the heat-transfer surface and lowers efficiency.
[Design Omission] It was not sized at 2× the maximum condensate rate and the capacity was not checked — the trap backed up.
1) Size the capacity at 2× the maximum condensate rate; the original 0.2 < 0.6 let water pool and cut efficiency 18%, so keep margin and drain freely;
2) Paralleling traps to raise capacity; a single valve is insufficient, so add more in parallel;
3) Fit a steam separator upstream to cut the load; wet steam adds load, so separate water;
4) Periodically measure capacity to check for decay; aging parts cut capacity, so monitor drainage;
5) Set a pooled-water level alarm; backup is hard to notice, so alarm;
6) Switch to a higher-capacity type to meet the peak; peaks exceed the design, so change type;
7) Insulate to avoid extra condensation; cold causes more condensate, so insulate;
8) Write capacity sizing into the design; the undersized selection was the cause of backup, so gate it at design.
GB/T 22654-2008 Steam traps - Technical specifications