E44-295 · Valve Selection and Internal Leakage · Pneumatic ball valve with GT pneumatic actuator · ★★
Water in the air supply condensed and rusted the cylinder bore, jamming the piston so the valve would not act; 4 failures a month.
[Water] Water in the compressed air condenses inside the cylinder and rusts the wall.
[Jam] Rust resists the piston and the valve will not move.
[Design Omission] No air dryer or filtration and no drainage — the pneumatic valve jammed.
1) Add an air dryer to hold the dew point ≤-20℃; water condensed and rusted the wall, jammed the piston, and caused 4 failures a month, so use dry air;
2) Fit an FRL unit on the air line (filter / regulator / lubricator); filtering water removes the rust source, so clean the air;
3) Fit a manual drain at the cylinder bottom and drain regularly; pooled water causes rust, so drain continuously;
4) Coat the cylinder bore with a rust inhibitor; rust is the jam source, so protect against it;
5) Periodically blow through the air line; fouling gradually jams it, so clean the line;
6) Set a low-air-pressure alarm; low pressure stops the valve, so alarm;
7) Switch to a stainless cylinder for wet service; wet environments rust easily, so make it moisture-resistant;
8) Bring air-supply quality into the design; the lack of control was the cause of jamming, so gate it at design.
GB/T 4213-2008 Pneumatic industrial-process control valves