E44-298 · Valve Selection and Internal Leakage · Spring safety valve A42Y-16C DN50 · ★★
A back pressure of 0.3MPa in the discharge line raised the set pressure by 20%, delayed response, and the valve popped only after 0.15MPa of overpressure.
[Back Pressure] Discharge-line resistance raises the pressure downstream of the valve, so more force is needed to open it.
[Delay] The raised set pressure delays response and overpressurizes.
[Design Omission] The discharge back pressure was not calculated and a balanced type was not used — the safety valve popped late.
1) Oversize the discharge pipe to hold back pressure ≤10% of set pressure; the original 0.3MPa raised opening 20%, delayed popping, and overpressured 0.15MPa, so lower the back pressure;
2) Switch to a balanced-bellows type resistant to back pressure; the balanced type is unaffected by back pressure, so resist it;
3) Keep the discharge pipe short, straight, and with few bends to cut resistance; bends add resistance, so discharge cleanly;
4) Keep the outlet away from the pressure tap; back pressure transmits back, so discharge remotely;
5) Periodically clear obstructions from the discharge pipe; blockage raises back pressure, so clean it;
6) Account for back-pressure correction when setting; back pressure raises the opening pressure, so correct it;
7) Provide a dedicated discharge header; a shared one causes back pressure, so use a dedicated line;
8) Bring back pressure into the selection calculation; the uncalculated back pressure was the cause of delay, so gate it at design.
GB/T 12243-2005 Spring-loaded direct pressure relief safety valves