E44-593 · Seal Leakage · Steam Trap Packing · ★★
Steam leakage, packing loose, dripping steam
[Mechanism] Loose packing leaks steam.
[Calculation] The looseness leaves a gap that leaks steam.
[Design Omission] The packing was not tightened, no packing was selected and nothing was inspected - it stayed loose.
1) Tighten the packing box to a packing pressure of 0.1MPa (torque wrench); the original looseness left the specific pressure insufficient and steam dripped through the stem gap, and raising it to 0.1 to 0.15MPa compacts the packing and stops the dripping;
2) Change to a temperature-resistant packing (flexible graphite or nickel based); the original packing was loose and steam above 180C ages it quickly, and a temperature-resistant material keeps its resilience;
3) Top up the packing to fill the box (stagger the cuts 120 degrees); too little packing cannot be compacted and stays loose, and topping up fills the box;
4) Add a Belleville spring washer to prevent loosening (disc springs); vibration loosens the bolts and the packing springs back and leaks, and the washer prevents that;
5) Check for steam dripping (count every shift); the leak develops gradually into dripping, so the drips are counted;
6) Select a soft packing that compacts (flexible graphite with rebound >40%); a hard packing cannot fill the micro-gap on the stem, and a soft one conforms to the stem;
7) Apply sealing grease (high-temperature grease); a dry gap lets the medium seep straight through, and the grease fills the gap;
8) Write the packing tightening into the maintenance card; the original failure to tighten was the root cause of the looseness, so the maintenance card closes the loop.
GB/T 12250-2005 Steam Traps