E44-360 · Water Hammer and Pressure Surge · Slow-closing check valve, oil-cylinder leak · ★★
A leaking slow-closing oil cylinder shortened the closure time to 1s; at pump shutdown Δp=1.1MPa exceeded the allowable limit and the valve disc shattered.
[Mechanism] The leaking oil cylinder defeated the slow closure, making it nearly fast and causing impact.
[Calculation] Δp=1.1 exceeded the allowable limit and shattered the disc.
[Design Omission] The oil cylinder was not kept sealed and the closure time was never tested, so the valve failed.
1) Repair the oil-cylinder seal to restore a 3~5s slow closure, because the leak shortened closure to 1s, drove Δp=1.1 beyond the limit and shattered the disc; hence restored slow closure;
2) Periodically test the closure time and check the curve, because drift makes it fast; hence time testing;
3) Provide a backup twin check valve, because a single valve failure is risky; hence dual protection;
4) Check Δp with a margin, because the uncalculated value exceeded the limit; hence accurate calculation;
5) Close the outlet valve first when stopping the pump, because a direct stop generates hammer; hence close first;
6) Install a surge arrester to cut the peak, because the wave amplitude exceeds the limit; hence peak absorption;
7) Monitor the oil-cylinder oil level, because a leak grows unnoticed; hence oil monitoring;
8) Put oil-cylinder maintenance into the procedures, because the lack of it was the root cause of the failure; hence procedural control.
GB/T 32284-2015 Code for design of pump stations - Water hammer protection