E44-379 · Water Hammer and Pressure Surge · Feed pump DG high pressure · ★★★
A feed-pump trip let boiler-side backflow stack on it; Δp=2.0MPa exceeded the pipe rating of 1.6 and shattered the feedwater valve.
[Mechanism] A high-pressure trip lets boiler-side backflow stack waves.
[Calculation] Δp=2.0 exceeded 1.6 and shattered the valve.
[Design Omission] No fast-closing check and no relief were provided, so the feed pump suffered hammer.
1) Fit a fast-closing check at the pump outlet to prevent boiler backflow, because the trip let backflow stack, Δp=2.0 exceeded the limit and shattered the valve; hence stop backflow;
2) Provide a drain valve to reduce the stacked pressure, because high static pressure makes stacking large; hence relief reduction;
3) Check the stacked pressure ≤ allowable, because stacking exceeds the limit; hence stacked calculation;
4) Up-rate the pipe to ≥2.5, because the allowable is low; hence higher rating;
5) Close slowly to avoid reclosure collision, because the collision generates hammer; hence slow closing;
6) Install a surge arrester to cut the peak, because the wave amplitude is large; hence peak absorption;
7) Recheck by water-hammer simulation, because estimates fall short; hence simulation;
8) Write high-pressure protection into the design, because the lack of it was the root cause of the hammer; hence design control.
GB/T 32284-2015 Code for design of pump stations - Water hammer protection