E44-378 · Water Hammer and Pressure Surge · Fire pump XBD direct start · ★★★
Direct startup of the fire pump took the flow from 0 to rated, Δp=ρcΔv=1.0MPa exceeding the pipe rating of 0.8, and broke two indoor hydrant cabinets.
[Mechanism] A sudden flow rise makes v jump, generating the wave Δp=1.0.
[Calculation] The exceeded limit of 0.8 broke the hydrant cabinet.
[Design Omission] No soft start and no loop buffering were provided, so fire-pump startup caused hammer.
1) Use a fire-pump soft start or star-delta to limit the ramp, because direct start drove Δp=1.0 beyond 0.8 and broke the cabinet; hence gentle start reduces the wave;
2) Provide a pressure-maintenance tank indoors to buffer the start wave, because startup also generates hammer; hence buffering;
3) Check the start Δp≤pipe rating, because the uncalculated value broke it; hence accurate calculation;
4) Up-rate the pipe network to ≥1.6, because the allowable is low; hence higher rating;
5) Fit a relief valve to cap the peak, because the amplitude exceeds the limit; hence relief;
6) Periodically test the start curve, because drift makes it abrupt; hence start test;
7) Use a loop network for pressure-divided water supply, because a single line has strong waves; hence loop network;
8) Write soft start into the control logic, because the original direct start was the root cause of the hammer; hence control discipline.
GB/T 32284-2015 Code for design of pump stations - Water hammer protection