E44-386 · Water Hammer and Pressure Surge · Piping Natural Frequency Near Hammer · ★★★
The hammer frequency approaches the piping natural frequency, causing resonance; the amplitude amplifies 3× and the supports detach by weld failure.
[Frequency Proximity] The hammer frequency approaches the natural frequency, causing resonance and 3× amplitude amplification.
[Weld Detachment] The large amplitude tears the supports loose at the welds.
[Design Omission] No frequency avoidance or stiffness tuning was done — resonant coupling resulted.
1) Change piping stiffness/supporting to move the natural frequency away from the hammer frequency: proximity caused resonance, 3× amplification and weld detachment; frequency avoidance is used;
2) Run a piping modal analysis to find the natural frequency: hidden frequencies are hard to detect, so modal analysis is used;
3) Install pulsation dampers to absorb vibration: vibration energy is high, so damping is used;
4) Eliminate hammer at source to lower the source amplitude: a large source couples strongly, so the source is cut;
5) Densify and reinforce the supports: weld detachment was imminent, so supports are anchored;
6) Limit start/stop rates to avoid excitation: fast changes excite vibration, so rates are limited;
7) Run combined water-hammer + vibration simulation: a standalone analysis misses the coupling, so combined simulation is used;
8) Write frequency avoidance into the design: the original frequency proximity was the root cause of the coupling, so design review enforces it.
GB/T 32284-2015 Code for design of pump stations - Water hammer protection