E44-387 · Water Hammer and Pressure Surge · Long-Span Pipe Low Frequency · ★★
Long spans give a natural frequency of 8Hz, near the hammer frequency of 10Hz, so coupling is likely and large vibration starts on pump trip.
[Low Frequency] Long spans give a natural 8Hz, near the hammer at 10Hz.
[Coupling] Frequencies that are close couple readily into vibration.
[Design Omission] Spans were not controlled and stiffness was not raised — near-frequency vibration resulted.
1) Shorten spans or add supports to raise the natural frequency away from the hammer: long spans gave natural 8 near hammer 10 and easy coupling; shortening spans moves away;
2) Check the natural frequency to keep a ±30% margin from the hammer frequency: closeness couples, so a clear band is kept;
3) Provide dynamic supports to absorb energy: vibration energy is high, so dynamic supports are used;
4) Eliminate hammer at source to lower the source amplitude: a large source couples strongly, so the source is cut;
5) Add mass or change the pipe section to tune the frequency: the frequency must be shifted, so tuning is used;
6) Periodically measure vibration to find near frequencies: hidden frequencies are hard to detect, so vibration measurement is used;
7) Run combined water-hammer + modal simulation: a standalone analysis misses it, so combined simulation is used;
8) Write spans into the design: the original long spans were the root cause of the frequency, so design review enforces them.
GB/T 32284-2015 Code for design of pump stations - Water hammer protection