E44-400 · Water Hammer and Pressure Surge · Siphon Flow Break · ★★
Flow break in a siphon separates the liquid column; on refill the collision gives Δp=1.1MPa over the allowable limit, and the pipe collapsed and leaked.
[Flow Break] Siphon collapse separates the column, and the refill causes a collision.
[Collapse] The negative wave let the thin wall buckle and leak.
[Design Omission] No full-flow assurance and no make-up pressure — break-induced hammer.
1) Fit a foot valve at the siphon inlet to keep the flow full and prevent breakage; the break split the column, refill drove Δp to 1.1 over the limit and buckled the line, so maintain full flow;
2) Install a vacuum breaker at the high point to slow refilling, because the refill collision generates hammer; hence slow refill;
3) Upgrade the pipe rating to resist negative-pressure collapse; vacuum buckled the wall, so raise the capacity;
4) Add a surge arrester to cushion the refill; refill collision generates hammer, so absorb the peak;
5) Use a slow-closing check valve to prevent backflow; reverse flow splits the column, so close slowly;
6) Run a water-hammer simulation to locate the separation point; it was hidden, so simulate;
7) Close the valve first and then stop the pump; a direct stop breaks the siphon, so close first;
8) Write siphon protection into the design; the missing full-flow assurance was the root cause, so close the loop at design.
GB/T 32284-2015 Code for design of pump stations - Water hammer protection