E44-1045 · Water Hammer and Pressure Surge · Valve · ★★
Quick-closure hammer, vibration, cracking
[Mechanism] A manually or motor-operated valve closed rapidly; the momentum water column in the pipe stops abruptly, generating a water-hammer pressure rise.
[Calculation] DN150 valve, 1s closure, v=2.5m/s; ΔP=ρcΔv=1000×1100×2.5=2.75MPa; exceeding the pipe allowable of 2.5MPa, and the joint leaked.
[Design Omission] No limit on valve-closing speed, no calculation of quick-closure hammer, and no slow closure.
1) Limit the valve-closing speed (closure ≥10s); sudden closure causes hammer, and slow closure cuts it, reducing hammer;
2) Check the closure time so ΔP≤0.5MPa (was 2.75); fast closing causes hammer, and a correct time keeps it controlled;
3) Add a slow-closing actuator (motor-controlled speed closure); hard closure cracks the pipe, and slow closure protects it;
4) Provide a surge tank (1m³ to absorb energy); sudden changes have no buffer without a tank, and the tank absorbs them, cutting the peak;
5) Run a water-hammer test (measured peak ≤0.9MPa); the hammer had never been calculated, and the measurement confirms control, so set the peak by data;
6) Install a pressure recorder (to watch the peak); hammer first shows up as a pressure spike, so early warning gives advance notice;
7) In operation, control the hand feel when closing valves (no slamming shut); sudden closure causes hammer, and speed control stabilizes it, preventing hammer in service;
8) Write the speed-limit hammer calculation into the specification; the root cause of valve quick-closure hammer is no speed limit and no hammer calculation, so the specification gates it.
GB/T 20801.3-2020 Design code for industrial metallic piping