E44-1046 · Water Hammer and Pressure Surge · Surge Tank · ★★
No vessel, hammer, vibration
[Mechanism] The system had no surge tank; water-hammer energy from any sudden flow change had nowhere to be absorbed, and the peak hit the equipment directly.
[Calculation] Pump discharge L=250m; on pump trip ΔP=1000×1000×2.2=2.2MPa; with no tank to absorb it, the peak was transmitted fully to the pump and valves, which damaged seals.
[Design Omission] No air-surge vessel was provided, buffer volume was not calculated, and precharge pressure was not checked.
1) Provide an air-surge vessel (2m³ volume, precharged 0.4MPa); no vessel causes hammer, and the vessel absorbs it, cutting the peak;
2) Check the vessel volume so it absorbs ΔP≤0.5MPa (was 2.2); a small vessel causes hammer, and a correct volume keeps it controlled;
3) Provide a slow-closing check valve (10s closure); sudden closure causes hammer, and slow closure cuts it, protecting the pipe;
4) Raise the precharge pressure to match (0.9×static pressure); low precharge causes hammer, and higher precharge absorbs energy;
5) Run a water-hammer test (measured peak ≤0.9MPa); the hammer had never been calculated, and the measurement confirms control, so set the peak by data;
6) Install pressure monitoring (to watch the peak); hammer first shows up as a pressure spike, so early warning gives advance notice;
7) In operation, change flow smoothly (no sudden stops or starts); sudden changes cause hammer, and smooth changes stabilize it, preventing hammer in service;
8) Write vessel sizing and volume check into the calculation report; the root cause of no-vessel hammer is no buffer and no volume calculation, so calculations gate it.
GB/T 20801.3-2020 Design code for industrial metallic piping