E44-119 · Two-Phase Flow and Air Binding · Siphon Water Pipeline · ★★
Air was not fully vented from the siphon crown; in service it accumulated and broke the flow, cutting downstream supply.
[Flow Break] Gas accumulates at the pipe crown and shrinks the flow area.
[Calculation] The air plug reduces the effective bore and cuts off the flow.
[Design Omission] No vent valve — the flow broke.
1) Fit an automatic vent at the pipe crown to release accumulated gas; the air plug shrank the flow, so keep the passage open;
2) Thoroughly fill and vent the line before priming the siphon; a fully vented start stays stable, so the flow never breaks;
3) Add a surge tank at the crown to hold gas; temporary gas storage keeps the plug from forming, so reduce breakage;
4) Control the velocity to prevent air entrainment; high v picks up gas, so keep the flow steady;
5) Fit a vacuum breaker to prevent siphon collapse; it is a safety measure, keeping the situation controllable;
6) Monitor the air-plug location in operation; knowing where the plug is allows early venting;
7) Test-run to verify continuous discharge with no flow break; the design requires measured verification, so confirm at handover;
8) Write venting into the siphon design; the missing vent was the main cause, so lock in the fix to prevent recurrence.
GB/T 20801.3-2020 Pressure piping code - Industrial piping - Design