E44-120 · Two-Phase Flow and Air Binding · Shell Side of Shell-and-Tube Heat Exchanger · ★★
Noncondensables accumulating on the shell side dropped the overall heat-transfer coefficient K from 800 to 450W/(m²·K), and the outlet temperature failed to meet spec.
[Air Binding] Noncondensables hug the tube wall and form a gas film.
[Calculation] The gas film adds large thermal resistance; K dropped 40%.
[Design Omission] No high-point vent — reduced heat transfer.
1) Fit a vent at the shell-side high point to bleed noncondensables periodically; the gas film added thermal resistance, so K recovers;
2) Lay the shell side on a slope toward the vent; correct slope gathers gas at the crown, making it easy to vent;
3) Monitor the trend of overall K; a falling K warns of gas buildup, so vent early;
4) Control the source of noncondensables (e.g. deaeration); cutting the source reduces accumulation, so stay steady;
5) Fit inlet/outlet temperature-difference points; a wide ΔT warns of falling K, keeping the condition known;
6) Periodically bleed crown gas to keep the shell liquid-full; full liquid coverage ensures enough heat-transfer area, meeting spec;
7) Test-run and measure K to the design value; the design requires measured verification, so confirm at handover;
8) Write venting into the heat-exchanger design; the missing vent was the main cause, so lock in the fix to prevent recurrence.
GB/T 151-2014 Heat exchangers