E44-450 · Two-Phase Flow and Gas Binding · Gas in Level-Gauge Impulse Line · ★★
Gas collecting in the impulse line distorted the differential pressure, showing a false level off by 30%, and causing overflow or running dry.
[Gas Accumulation] Gas in the impulse line distorted the differential pressure, giving a false level off by 30%.
[Hazard] The error caused overflow or running dry.
[Design Omission] No impulse-line venting and no balance chamber; gas binding caused the false level.
1) Provide impulse-line venting and a balance chamber; gas distorted the differential pressure, giving a 30% false level and overflow/dry-out, so venting and balance restore the true level;
2) Take the pressure tap low to keep gas out; gas collects at the top, so tap low;
3) Provide dual-level comparison; a single gauge easily reads false, so compare two;
4) Periodically vent and zero-calibrate; gas accumulates gradually into a false reading, so vent and calibrate;
5) Select non-contact gauges such as radar; differential-pressure gauges are upset by gas, so change the type;
6) Interlock the level to prevent overflow and dry-out; the false reading is hazardous, so interlock it;
7) Keep the high and low pressure sides at equal temperature; a temperature difference causes a differential error, so equalize temperature;
8) Write impulse-line venting into the design; gas accumulation was the root cause of the false level, so the design gates it.