E44-1052 · Two-Phase Flow and Air Binding · Piping · ★★
Two-phase vibration, noise, cracking
[Mechanism] Unstable two-phase flow patterns excite low-frequency piping vibration, loosening supports and hanging frames and fatiguing welds.
\n[Calculation] DN250 pipe, two-phase flow excitation f=6Hz, natural frequency fn=6.5Hz near resonance, vibration amplitude 0.6mm, 3 loose support bolts.
\n[Design Omission] Flow pattern not stabilized, supports not reinforced, natural frequency not calculated.
1) Stabilize the flow pattern (adjust the gas-liquid ratio to leave the resonance band); since pattern changes cause vibration, stabilizing avoids it, reducing vibration;
\n2) Verify the natural frequency (keep fn at least ±20% away from the excitation frequency); since near-resonance causes vibration, the frequency check avoids resonance, preventing resonance;
\n3) Add and stiffen supports (tighten spacing to 3m); since sway causes vibration, firm supports reduce it, lowering vibration;
\n4) Add dampers (viscous c=15kN·s/m); since swinging causes vibration, damping suppresses it, dissipating energy;
\n5) Run a vibration test (monitor amplitude ≤0.2mm); since vibration was never verified, measured data confirms stability, so vibration is confirmed by data;
\n6) Fit vibration monitoring (alarm on threshold), since vibration first shows as amplitude for early warning, monitoring and alerting;
\n7) Keep operating conditions steady in service (avoid the resonance band); since load changes excite vibration, stable operating conditions prevent it, suppressing vibration in operation;
\n8) Write flow-pattern stabilization and support details into the assembly card; since the root cause of two-phase vibration is an unstabilized pattern and unrestrained supports, the assembly stage provides the check.
GB/T 11349.1-2006 Mechanical vibration and shock