E44-122 · Filter Clogging and Contamination · Steam Y-Strainer · ★★
A 200-mesh (too fine) screen was selected; debris plugged it, the pressure differential reached 0.15MPa, and steam supply to the downstream side was cut off.
[Oversize mesh] Too fine a mesh plugs easily.
[Calculation] When screen pores are < the debris particle size, it plugs and Δp spikes.
[Design Omission] The mesh size was not selected by medium dirt load, causing plugging.
1) Select a suitable mesh (e.g. 40–80 mesh) by medium dirt load and particle size, because the mesh must match the debris, thereby avoiding plugging;
2) Install a duplex strainer with online switching, because switchable units allow element change without shutdown, thereby keeping continuity;
3) Choose a high dirt-holding-capacity element, because larger capacity means longer intervals, thereby reducing plugging;
4) Monitor differential pressure online and alarm for element change, because rising Δp foreshadows plugging, thereby changing early;
5) Add a desander or pre-filter upstream, because coarse debris is removed first, thereby reducing plugging;
6) Clean the screen periodically and record the interval, because a known interval enables planned maintenance;
7) On the trial run, verify Δp≤0.05MPa and stable flow, because design requirements must be measured, thereby confirming delivery;
8) Include mesh sizing in the filtration design, because over-sizing is the root cause, thereby institutionalizing prevention.
GB/T 20801.3-2020 Pressure piping code - Industrial piping - Design